The CXH18 Mining Intrinsically Safe Programmable Display Operation Box adopts an intrinsically safe design, suitable for use in mine shafts with risks of gas and coal dust explosions. The control box enables local control, data acquisition, transmission, and alarm functions. The operation box is equipped with a 10.1-inch color intrinsically safe touchscreen, offering clear display and convenient operation. Each box has an independent power supply to ensure safety during maintenance. It features an Ethernet data upload interface for data transmission with other substations and main stations. The internal controller integrates a dual-controller mode of PLC controller and mine Hong controller for user selection.
【Performance Characteristics】
1.Safe and Reliable:
·Intrinsically safe design for mining, explosion-proof display screen, suitable for flammable and explosive environments in mine shafts.
·Independent power supply for each operation box ensures safety during maintenance.
2.Powerful Functions:
·The operation box enables local control, data acquisition, transmission, and alarm functions.
·Features various operation buttons including knobs, push buttons, multi-position selector switches, and emergency stop switches.
3.Multiple Input/Output Channels:
·8 channels of passive contact signal input/output.
·12 channels of 4mA~20mA current analog signal input.
·9 channels of PT100 analog signal input.
4.Convenient Application:
·The operation box supports Ethernet optical/electrical signals, RS485 signals, and CAN signal transmission, facilitating network access.
·The 10.1-inch LCD touchscreen allows for easy human-machine interaction and operation.
【Product Parameters】
A.Power Supply
a) Rated Working Voltage: DC 12V; Max. Working Current: ≤1.0A;
b) Rated Working Voltage: DC 18V; Max. Working Current: ≤0.8A.
B. Input/output signals
a) 8-way passive contact signal input: When the input resistance is ≤ 300 Ω, corresponding logic "1", input resistance
When ≥ 90k Ω, the corresponding logic is "0";
b) 8-way passive contact signal output: when closed, inject 2mA, voltage drop not greater than 0.5V, when disconnected
The resistance shall not be less than 100k Ω.
c) 12 channels of 4-20 mA current type analog signal input;
d) 9-way resistance type analog signal input: corresponding to 100 Ω~138.5 Ω (0~100 ℃);
e) Analog input processing error: ≤ 1.0% (F.S.).
C. Ethernet electrical signal interface
a) Number of interfaces: 1 channel;
b) Transmission method: Full duplex, TCP/IP Ethernet signal transmission;
c) Transmission rate: 100Mbps;
d) Peak to peak value of signal voltage: ≤ 5 V;
e) Maximum transmission distance: 50 meters (using MHYV coal mine communication cable with a cross-sectional area of not less than
1.5mm2)。
D. Ethernet optical interface
a) Quantity: 2 routes;
b) Interface type: SC;
c) Transmission method: TCP/IP full duplex Ethernet optical signal transmission;
d) Transmission rate: 1000 Mbps;
e) Light emission power: -10~0dBm; (1310nm, single-mode dual fiber)
f) Receiver sensitivity: -25dBm; (1310nm, single-mode dual fiber)
g) Maximum transmission distance: 10km. (Using MGTSV single-mode optical cable; There are a total of 8 fiber optic contacts,Among them, there are 3 hot melt joints, 3 cold melt joints, and 2 movable connection points.
E. RS485 signal interface
a) Quantity: 1 route;
b) Transmission mode: half duplex, bipolar;
c) Transmission rate: 9600 bps;
d) Peak to peak voltage of signal operation: 2V to 12V;
e) Maximum transmission distance: 1km (MHYV 1.5mm2 mining communication cable).
F. CAN signal interface (Mine Hong controller)
a) Quantity: 1 route;
b) Transmission mode: half duplex, bipolar;
c) Transmission rate: 5kbps;
d) Peak to peak voltage of signal operation: 1V to 5V;
e) Maximum transmission distance: 3km (MHYV 1.5mm2 mining communication cable).
G. Function
a) The operation box has 32 button signals; 4-channel three gear selection button signal; 1-channel eight speed knob signal;
1 emergency stop button signal;
b) The operation box has 8 channels of passive contact signal input and output, and 12 channels of 4mA~20mA current type analog signals
Signal, 9-channel PT100 analog signal input;
c) The operation box has the function of transmitting Ethernet optical/electrical signals, RS485 signals, and CAN signals;
d) The operation box has a 10.1-inch LCD display screen, which displays the status of various input and output signals.
H. Intrinsic safety parameters:
a) 12V input terminal (4 channels, not common ground): Ui: 12.5V, Ii: 1.5A, Ci: 0 µ F, Li: 0 µ H.
b) 18V input terminal: Ui: 18.5V, Ii: 0.9A, Ci: 0 µ F, Li: 10 µ H.
c) Electrical signal terminal: Uo: 6.1V, Io: 310mA, C0: 10 μ F, Lo: 0.2mH.
d) RS485, CAN signal terminal: Uo: 5.88V, Io: 100mA, C0: 20 µ F, Lo: 5mH.
【Product Qualifications】